Skip to main content
PRODUCTS | ACCESSORIES
ECP APE 03

    Man in cold room alarm kit: consisting of control unit with acoustic / visual warning, comes complete with buffer battery and luminous emergency in-room pushbutton.
    The kit allows a person trapped inside the cold room to activate an acoustic-luminous alarm installed outside the room and so call for help. The system will work even in the event of a temporary power cut thanks to the buffer battery on the external unit.

      Applications
      • “Man in room” safety system for low-temperature rooms.

      Main characteristics
      • Complies to the UNI EN 378-1:2016, applicable to cold rooms at negative temperatures with a volume greater than 10 m3.
      • Emergency pushbutton to be fitted inside cold room. This is a luminous mushroom-shaped pushbutton with a N.C. contact. The pushbutton is illuminated by LEDs, thus making it easy to find even in the dark.
      • Acoustic-visual alarm control unit to be fitted outside the room. Features a siren and a flashing light and a buffer battery to provide power in the event of a black-out. Also has a clean contact (SPDT) that can be used to inhibit refrigeration, switch on the interior room light or activate other devices such as a dialer for remote alarm activation.
      Properties
      Dimension
      ECP APE 03
      Control unit: 203x193x79 mm
      Pushbutton: 85x85x85 mm
      Peso
      ECP APE 03
      2Kg
      Alimentazione principale
      ECP APE 03
      230 VAC 50/60 Hz
      Max consuption on main power supply
      ECP APE 03
      20 mA
      Battery
      ECP APE 03
      12 VDC Ni-MH 1300 mAh Complete recharge time : 110 h
      Autonomy
      ECP APE 03
      With 230 VAC power off (operation with charged buffer battery: about 14h) • With 230 AC power on: unlimited
      External module
      ECP APE 03
      IP 43 protection rating
      Working temperature
      ECP APE 03
      -5 ÷ +45°C
      Acoustic characteristics
      ECP APE 03
      Type: piezoelectric Sound power: 90 dB at 1m
      Visual warning
      ECP APE 03
      Red flashing led 12 VDC
      In-room emergency pushbutton
      ECP APE 03
      In-room emergency pushbutton red flashing LED 12 VDC NC contact Keyboard with IP 65 protection rating Operating temperature : -25 ÷ +70 °C
      Relè allarme / AUX
      ECP APE 03
      8A AC1 (SPDT)
      Working temperature
      ECP APE 03
      -5 ÷ +45°C
      Dimension
      ECP APE 03
      Connection Scheme
      ECP APE 03
      Technical Characteristics
      Outputs
      Ambient Condition
      Dimensions and Diagram