Skip to main content
PRODUCTS | ELECTRICAL BOARDS
ECP300 BASE4 VD

A LINE OF CONTROL PANELS FOR COLD ROOMS.

A LINE OF CONTROL PANELS FOR COLD ROOMS.
A LINE OF CONTROL PANELS FOR COLD ROOMS.

    A line of control panels for cold rooms with three-phase compressor up to 3 HP, specially designed for complete cold room management. Together with the various options, the different power ranges allow the user to select a unit that is “custom- made” to suit the refrigeration system.

    A LINE OF CONTROL PANELS FOR COLD ROOMS.
    A LINE OF CONTROL PANELS FOR COLD ROOMS.
      Applications
      • Complete control of three-phase static or ventilated refrigeration systems up to 3 HP, off-cycle or electrical defrosting.

      Options
      • Installation of magnetothermic protection devices instead of fuses.
      • Alarm output with free-voltage contact to activate further warning devices such as siren or dialer.
      • Pump-down compressor stop.
      • Hot-gas defrost control.
      Main characteristic
      • Direct control of compressor, condenser fans, compressor oil heater, defrosting heaters, evaporator fans, solenoid valve, room light and all standard-compliant electrical protection devices.
      • Compact, self-extinguishing ABS housing with IP65 protection rating and frontal circuit-breaker.
      • Electronic control with wide LED display and user-friendly keypad.
      • System status indicated by icons.
      • RS485 for connection to TeleNET industrial supervision network or Modbus-RTU standard protocol.
      Properties
      Dimension
      ECP300 BASE4 VD
      290x340x145 mm
      Weight
      ECP300 BASE4 VD
      5kg
      Front protection rating
      ECP300 BASE4 VD
      IP 65
      Power supply
      ECP300 BASE4 VD
      400 VAC ±10% 50/60 Hz
      Status indicator
      ECP300 BASE4 VD
      Led + Display
      Load type
      ECP300 BASE4 VD
      Three phase
      Working temperature
      ECP300 BASE4 VD
      -5 ÷ +50 °C
      Storage temperature
      ECP300 BASE4 VD
      -10 ÷ +70 °C
      Relative ambient humidity
      ECP300 BASE4 VD
      30% - 90% RH without condensate
      Reading range
      ECP300 BASE4 VD
      -45 ÷ +99°C
      Door lock main switch
      ECP300 BASE4 VD
      16 A
      Compressor protection
      ECP300 BASE4 VD
      Thermal relay
      General protection
      ECP300 BASE4 VD
      Fuses (option: magnetothermic protection)
      Control
      ECP300 BASE4 VD
      Pego
      Alarm signals
      ECP300 BASE4 VD
      Led + Buzzer
      Defrosting
      ECP300 BASE4 VD
      Electrical
      Ambient probe
      ECP300 BASE4 VD
      NTC 10 kΩ
      Evaporator probe 1
      ECP300 BASE4 VD
      NTC 10 kΩ
      Door switch
      ECP300 BASE4 VD
      Present
      High/low pressure switch
      ECP300 BASE4 VD
      Present
      Kriwan® connection
      ECP300 BASE4 VD
      Present
      Compressor
      ECP300 BASE4 VD
      2200W (0,5÷3 HP)
      Defrosting heaters 1
      ECP300 BASE4 VD
      4000W (AC1)
      Evaporator fans 1
      ECP300 BASE4 VD
      800W (1 PH)
      Condenser fans output 1
      ECP300 BASE4 VD
      800W (1 PH)
      Solenoid valve 1
      ECP300 BASE4 VD
      Present
      Compressor oil heater
      ECP300 BASE4 VD
      Present
      Room light
      ECP300 BASE4 VD
      Present
      2 Configurable relays
      ECP300 BASE4 VD
      Present
      Supervision
      ECP300 BASE4 VD
      TeleNet / Modbus-RTU
      Dimension
      ECP300 BASE4 VD
      ECP300 BASE4 VD
      Connection Scheme
      ECP300 BASE4 VD
      ECP300 BASE4 VD
      Technical Characteristics
      Inputs
      Outputs
      Dimensions and Diagram